中文 ENGLISH
Homepage  |  Favorites
Products
Catalog
Search
Contact

Tel:+86-21-54332015
Fax:+86-21-61927327
E-mail: info@seabil.com

 
Current Location:Home >> Regulation >> Fixed Pressure Water-Spraying And Water-Mist Fire extinguishing System
Back
Fixed Pressure Water-Spraying And Water-Mist Fire extinguishing System

 1 Application

This chapter details the specifications for fixed pressure water-spraying and water-mist fire-extinguishing systems as required by chapter II-2 of the Convention.
2 Engineering specifications
2.1 Fixed pressure water-spraying fire-extinguishing systems
2.1.1 Nozzles and pumps
2.1.1.1 Any required fixed pressure water-spraying fire-extinguishing system in machinery spaces shall be provided with spraying nozzles of an approved type.
2.1.1.2 The number and arrangement of the nozzles shall be to the satisfaction of the Administration and shall be such as to ensure an effective average distribution of water of at least 5 l/m2/min in the spaces to be protected. Where increased application rates are considered necessary, these shall be to the satisfaction of the Administration.
2.1.1.3 Precautions shall be taken to prevent the nozzles from becoming clogged by impurities in the water or corrosion of piping, nozzles, valves and pump.
2.1.1.4 The pump shall be capable of simultaneously supplying at the necessary pressure all sections of the system in any one compartment to be protected.
2.1.1.5 The pump may be driven by an independent internal combustion machinery, but, if it is dependent upon power being supplied from the emergency generator fitted in compliance with the provisions of regulation II-1/42 or regulation II-1/43 of the Convention, as appropriate, that generator shall be so arranged as to start automatically in case of main power failure so that power for the pump required by paragraph 2.1.1.4 is immediately available. The independent internal combustion machinery for driving the pump shall be so situated that a fire in the protected space or spaces will not affect the air supply to the machinery.
2.1.2 Installation requirements
2.1.2.1 Nozzles shall be fitted above bilges, tank tops and other areas over which oil fuel is liable to spread and also above other specific fire hazards in the machinery spaces.
2.1.2.2 The system may be divided into sections, the distribution valves of which shall be
operated from easily accessible positions outside the spaces to be protected so as not to be readily cut off by a fire in the protected space.
2.1.2.3 The pump and its controls shall be installed outside the space or spaces to be protected. It shall not be possible for a fire in the space or spaces protected by the water-spraying system to put the system out of action.
2.1.3 System control requirements
The system shall be kept charged at the necessary pressure and the pump supplying the water for the system shall be put automatically into action by a pressure drop in the system.
2.2 Equivalent water-mist fire-extinguishing systems
Water-mist fire-extinguishing systems for machinery spaces and cargo pump-rooms shall be approved by the Administration based on the guidelines developed by the Organization.
 
 
Back
Home  |  About Us  |  Products  |  Services  |  Projects  |  Regulation  |  Careers  |  Contact Us  |  Feedback
英海联国际集团有限公司
Seabil International Group Co., LTD
©2001-2025 Seabil International Group Co.,LTD. All Rights Reserved.